Duct Size Chart: CFM Reference Sheet

Standard Residential Friction Loss: 0.1 in. w.g. per 100 ft • Based on ACCA Manual D & ASHRAE Standards

HVAC Duct Calculator
www.hvacductcalculator.com
1. Round Duct CFM Chart Rigid Metal @ 0.1 FR
Dia. CFM Velocity Recommended Use
4" 37 CFM 426 FPM Bath exhaust
5" 67 CFM 492 FPM Small bedroom
6" 109 CFM 553 FPM Standard bedroom
7" 163 CFM 611 FPM Master bedroom
8" 232 CFM 666 FPM Living branch / trunk
9" 317 CFM 718 FPM Zone trunk
10" 419 CFM 768 FPM 1-Ton main trunk
12" 678 CFM 863 FPM 1.5–2 Ton main trunk
14" 1019 CFM 953 FPM 2.5-Ton trunk (953 FPM)
16" 1450 CFM 1039 FPM 3.5–4 Ton trunk
18" 1980 CFM 1120 FPM 5-Ton trunk / light comm.
20" 2615 CFM 1199 FPM Commercial trunk
2. Rectangular Duct CFM Chart Huebscher Equiv. @ 0.1 FR
Size (W×H) CFM Equiv. Velocity
8×6" 200 CFM 7.6" 599 FPM
10×6" 264 CFM 8.4" 634 FPM
12×6" 330 CFM 9.1" 661 FPM
10×8" 393 CFM 9.8" 708 FPM
12×8" 496 CFM 10.7" 743 FPM
14×8" 600 CFM 11.5" 772 FPM
16×8" 706 CFM 12.2" 795 FPM
18×8" 814 CFM 12.9" 814 FPM
20×8" 922 CFM 13.5" 830 FPM
12×10" 673 CFM 12.0" 807 FPM
14×10" 819 CFM 12.9" 843 FPM
16×10" 969 CFM 13.7" 872 FPM
18×10" 1120 CFM 14.5" 896 FPM
20×10" 1274 CFM 15.2" 917 FPM
3. Flexible Duct CFM Chart Keep velocity < 700 FPM
Dia. Stretched Installed Velocity
4" Flex 33 CFM 30 CFM 344 FPM
5" Flex 59 CFM 54 CFM 396 FPM
6" Flex 96 CFM 88 CFM 448 FPM
7" Flex 144 CFM 132 CFM 494 FPM
8" Flex 204 CFM 188 CFM 539 FPM
9" Flex 279 CFM 256 CFM 579 FPM
10" Flex 369 CFM 338 CFM 620 FPM
12" Flex 597 CFM 548 CFM 698 FPM
14" Flex 897 CFM 823 CFM 770* FPM
16" Flex 1276 CFM 1172 CFM 839* FPM
4. Return Air Duct Sizing Quiet Target: 500–650 FPM
System Size Min. Round Min. Rectangular Design Velocity
1.0 Ton (400 CFM) 12" 14×8" / 12×10" 509 FPM
2.0 Ton (800 CFM) 14"–16" 20×10" / 24×8" 573 FPM
3.0 Ton (1,200 CFM) 18" 26×10" / 22×12" 611 FPM
4.0 Ton (1,600 CFM) 20" 30×10" / 26×12" 660 FPM
5.0 Ton (2,000 CFM) 22"–24" 34×10" / 30×12" 679 FPM
Notes: Flex duct is derated ~20% for wire friction and 15% standard installation sag (*exceeds 700 FPM). Return ducts require lower velocity (<650 FPM) to avoid grille noise.